Limitor® - NF/UTE Back-up Fuses, 7,2kV to 24kV - Type FR
FR-type fuses are designed to protect HV/LV power distribution transformers. Designed to be coordinated with other equipment, these current limiting fuse-links interrupt fault currents before they reach their peak. The fault current is interrupted inside the fuse-link body and although this is very fast, there is no sign of it outside. The 24kV fuses were specially designed with very low power losses, for use in SF6-insulated or compact air-insulated fused switchgear combinations The main elements in these fuses are: a barrel of class F insulating synthetic material, nickel plated aluminium end contacts, pure silver fuse elements and a composite material fuse element holder to withstand high temperatures. Thanks to their structure, based on a synthetic material, FR fuse-links are the perfect answer to the stress involved in use inside HV bays and fuse-link chambers.
FR-type fuses are designed to protect HV/LV power distribution transformers. Designed to be coordinated with other equipment, these current limiting fuse-links interrupt fault currents before they reach their peak. The fault current is interrupted inside the fuse-link body and although this is very fast, there is no sign of it outside. The 24kV fuses were specially designed with very low power losses, for use in SF6-insulated or compact air-insulated fused switchgear combinations The main elements in these fuses are: a barrel of class F insulating synthetic material, nickel plated aluminium end contacts, pure silver fuse elements and a composite material fuse element holder to withstand high temperatures. Thanks to their structure, based on a synthetic material, FR fuse-links are the perfect answer to the stress involved in use inside HV bays and fuse-link chambers.
Product data sheets
- DS-Limitor-HV-fuse-links-HTA-UTE-7-2kV-24kV-Type-FR-EN
pdf - 1.16 MB
Charts
- CHT_Limitor-HV-fuse-links-HTA-UTE-7-2kV-24kV
pdf - 1.5 MB
Compliance
- COM-REACH-declaration-0056-FRxx-Limitor-fuses-Medium-Voltage
pdf - 244.77 KB
Key features & benefits
Superior mechanical strength
Outstanding withstand to operating stresses
100% synthetic structure
Reduce power losses by 30 to 40% (24kV)
Average type striker: force 1 ±0.5 Joules
High breaking capacity
High current limitation
EDF Approval which guarantees high performances and quality of fuses manufactured (24kV)
In accordance with:
IEC 62271-105
IEC 62271-107
IEC 60787
IEC/TR 62655
Applications
HV Transformers protection
Fused switch gear combination
Best used in SF6 insulated switch gear and compact switch gear
For indoor use
Operating temperature: -25°C to +40°C
Voltage Range | 7.2 ... 24 kV |
Amperage Range | 6.3 ... 125 A |
Reach Compliant | Yes |
Reference Finder
Scroll
Item number | Ampere rating | Fuse size | Clearing I2t At Rated Voltage | Indication System | Product weight |
---|---|---|---|---|---|
A1045212 - FRECO240V50P See product
|
50A | d=55mm, L=520mm | 39.3kA²s | Yes | 2.3kg |
A210243 - FR120V43 See product
|
43A | d=55mm, L=520mm | 12kA²s | No | 2.1kg |
A227585 - FR72V16 See product
|
16A | d=55mm, L=520mm | 1.6kA²s | No | 2.1kg |
B1043534 - FRECO240V16 See product
|
16A | d=55mm, L=520mm | 4.7kA²s | No | 2.1kg |
B210244 - FR120V63 See product
|
63A | d=55mm, L=520mm | 24kA²s | No | 2.1kg |
B227586 - FR72V32 See product
|
32A | d=55mm, L=520mm | 6kA²s | No | 2.1kg |
C227587 - FR72V43 See product
|
43A | d=55mm, L=520mm | 12kA²s | No | 2.1kg |
D210246 - FR120V6,3P See product
|
6.3A | d=55mm, L=520mm | 0.3kA²s | Yes | 2.3kg |
D227588 - FR72V63 See product
|
63A | d=55mm, L=520mm | 24kA²s | No | 2.1kg |
E210247 - FR120V16P See product
|
16A | d=55mm, L=520mm | 1.6kA²s | Yes | 2.3kg |