Limitor® - NF/UTE Back-up Fuses, 7,2kV to 24kV - Type FR
FR-type fuses are designed to protect HV/LV power distribution transformers. Designed to be coordinated with other equipment, these current limiting fuse-links interrupt fault currents before they reach their peak. The fault current is interrupted inside the fuse-link body and although this is very fast, there is no sign of it outside. The 24kV fuses were specially designed with very low power losses, for use in SF6-insulated or compact air-insulated fused switchgear combinations The main elements in these fuses are: a barrel of class F insulating synthetic material, nickel plated aluminium end contacts, pure silver fuse elements and a composite material fuse element holder to withstand high temperatures. Thanks to their structure, based on a synthetic material, FR fuse-links are the perfect answer to the stress involved in use inside HV bays and fuse-link chambers.
FR-type fuses are designed to protect HV/LV power distribution transformers. Designed to be coordinated with other equipment, these current limiting fuse-links interrupt fault currents before they reach their peak. The fault current is interrupted inside the fuse-link body and although this is very fast, there is no sign of it outside. The 24kV fuses were specially designed with very low power losses, for use in SF6-insulated or compact air-insulated fused switchgear combinations The main elements in these fuses are: a barrel of class F insulating synthetic material, nickel plated aluminium end contacts, pure silver fuse elements and a composite material fuse element holder to withstand high temperatures. Thanks to their structure, based on a synthetic material, FR fuse-links are the perfect answer to the stress involved in use inside HV bays and fuse-link chambers.
Product data sheets
- DS-Limitor-HV-fuse-links-HTA-UTE-7-2kV-24kV-Type-FR-EN
pdf - 877.16 KB
Brochures and Flyers
- FLY_Limitor_HTA-fuses-24kV-UTE
pdf - 2.21 MB
Charts
- CHT_Limitor-HV-fuse-links-HTA-UTE-7-2kV-24kV
pdf - 1.5 MB
Compliance
- COM-REACH-declaration-0056-FRxx-Limitor-fuses-Medium-Voltage
pdf - 368.44 KB
Key features & benefits
Superior mechanical strength
Outstanding withstand to operating stresses
100% synthetic structure
Reduce power losses by 30 to 40% (24kV)
Average type striker: force 1 ±0.5 Joules
High breaking capacity
High current limitation
EDF Approval which guarantees high performances and quality of fuses manufactured (24kV)
In accordance with:
IEC 62271-105
IEC 62271-107
IEC 60787
IEC/TR 62655
Applications
HV Transformers protection
Fused switch gear combination
Best used in SF6 insulated switch gear and compact switch gear
For indoor use
Operating temperature: -25°C to +40°C
| Voltage Range | 7.2 ... 24 kV |
| Amperage Range | 6.3 ... 125 A |
| CE Conformity | 1 |
| Reach Compliant | Yes |