Back
Where to buy Contact us

MULTIVERT® 400A and i-Xtensio 400A, Size 2, 690VAC

Approvals & Standards
IEC/EN 60 947-3
For NH-fuse links size 1 & 2 in accordance with IEC/EN 60 269-2, VDE 0636-2

MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 400A are for installation on to 185mm bus bar systems. MULTIVERT® 400A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 2: 400A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance. 2 alternative designs are available for a user-friendly and adaptable installation according to the needs: - The standard design offers a very compact solution with an installation depth of only 123mm, enabling to save space in the Power distribution cabinets - The i-Xtensio design offers a user-friendly mounting solution for current transformers at the back of the Multivert and more standard installation depth of 150mm

MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 400A are for installation on to 185mm bus bar systems. MULTIVERT® 400A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 2: 400A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance. 2 alternative designs are available for a user-friendly and adaptable installation according to the needs: - The standard design offers a very compact solution with an installation depth of only 123mm, enabling to save space in the Power distribution cabinets - The i-Xtensio design offers a user-friendly mounting solution for current transformers at the back of the Multivert and more standard installation depth of 150mm

Key features & benefits

  • Installation on to 185 mm bus bar system

  • Standard design with M 12 screws: M = 35 ±3Nm

  • Direct installation without drilling with hooked clamps possible

  • Symmetrical switch - top/bottom cable terminal connection

  • Touch protection IP 30 with central cover

  • Varieties of cable termination: bolt, insert nut, V-terminal

  • Integrated measuring transformer (optional) with unchanged installation depth

  • Safe on load connection/disconnection in accordance with IEC 60947-3

  • i-Xtensio new range available for increased installation depth of 150mm and for external Current Transformer mounting possibility

Applications

  • Feeder pillars

  • Transformer substations

  • Switch boards for industrial applications

  • Residential and industrial distribution units

  • Cable distribution cabinets

Technical Specifications
Frequency (Hz) 50 ... 60 Hz
Short Circuit Current Rating (SCCR) 120kA@Ue = AC 400 V; Ie = 400 A / 120kA@Ue = AC 500 V; Ie = 400 A / 120kA@Ue = AC 690 V; Ie = 315 A / 100kA@Ue = AC 690 V; Ie = 400 A
CE Conformity Yes
Reach Compliant Yes
Degree of Protection (IP) IP30

Reference Finder

Item number Fuse size Number of poles Product weight
A1023201 - 1.220.000 See product
2 3-Pole 4.38kg
B1023202 - 1.220.900 See product
2 3-Pole 5.45kg
C1023203 - 1.200.064 See product
2 3-Pole 4.7kg
D1023204 - 1.200.074 See product
2 3-Pole 4.7kg
E1023205 - 1.200.084 See product
2 3-Pole 4.7kg
F1023206 - 1.200.094 See product
2 3-Pole 5.4kg
G1023207 - 1.260.000 See product
2 3-Pole 4.68kg
H1023208 - 1.270.000 See product
2 3-Pole 4.78kg
J1002187 - 1.200.000 See product
2 3-Pole 4.6kg
J1023209 - 1.270.100 See product
2 3-Pole 5.1kg
Back to top